The Fluke 1736/EUS Three-Phase Power Logger (international version) is built with Fluke Connect mobile app and desktop software compatibility gives you the data you need to make critical power quality and energy decisions in real-time. The best test tool f
The Fluke 1736/EUS Three-Phase Power Logger (international version) is built with Fluke Connect mobile app and desktop software compatibility gives you the data you need to make critical power quality and energy decisions in real-time. The best test tool for conducting energy studies and basic power quality logging, the 1736 automatically captures and logs over 500 power quality parameters so you have more visibility into the data you need to optimize system reliability and savings.
Features:
Automatically capture and log voltage, current, power, harmonics and associated power quality values.
Fluke Connect compatible: View data locally on the instrument or via Fluke Connect mobile app and desktop software.
Highest safety rating in the industry: 600 V CAT IV/1000 V CAT III rated for use at the service entrance and downstream.
Measure all three phases and neutral using the included 4 flexible current probes.
More than 20 separate logging sessions can be stored
Includes event waveform snapshot and high resolution RMS profile, along with date, timestamp and severity to help pinpoint potential root causes ofpower quality issues.
Colored touch-screen with optimized user-interface
Complete “in-the-field” setup through the front panel or Fluke Connect App
Energy Analyze Plus application software: Download and analyze every detail of energy consumption and power quality state of health with our automatedreporting.
Accuracy | ||||
Parameter | Range | Resolution | Intrinsic Accuracy at Reference Conditions (% of Reading +% of Full Scale) |
|
Voltage | 1000 V | 0.1 V | (0.2% + 0.01%) | |
Current: Direct input | i17xx-flex 1500 12″ | 150 A | 0.1 A | (1% + 0.02%) |
1500 A | 1 A | |||
i17xx-flex 3000 24″ | 300 A | 1 A | (1% + 0.03%) | |
3000 A | 10 A | |||
i17xx-flex 6000 36″ | 600 A | 1 A | (1.5% + 0.03%) | |
6000 A | 10 A | |||
i40s-EL clamp | 4 A | 1 mA | (0.7% + 0.02%) | |
40 A | 10 mA | |||
Frequency | 42.5 Hz to 69 Hz | 0.01 Hz | (0.1%) | |
Auxillary input | 10 V dc | 0.1 mV | (0.2% + 0.02%) | |
Voltage min/max | 1000 V | 0.1 V | (1% + 0.1%) | |
Current min/max | Defined by accessory | Defined by accessory | (5% + 0.2%) | |
THD on voltage | 1000% | 0.1% | 0.5 | |
Voltage harmonics 2nd to 50th | 1000 V | 0.1 V | 10 V: 5% of reading | |
< 10 V: 0.5V | ||||
Current harmonics 2nd to 50th | Defined by accessory | Defined by accessory | 3% of current range: 5% of reading | |
< 3% of current range: 0.15% of range | ||||
Unbalance | 100% | 0.1% | 0.2 | |
$25